COMPLETE ELECTRICAL OCT24 9305Tupack Rhea, P.E.
Professional Engineer; Florida Registration # 40217
12310 SW 39th Street, Miami, Fl 33175: Phone: (305) 569 0191
tupack@tupack.net
Miami, OCTOBER 9, 2024
Town of Medley
Building and Zoning Department
Town of Medley
7777 NW 72 Avenue
Medley,
Attn.: Miguel Nunez, Building Official
RE: Electrical Re Certification of 9305 NW 101 St. Folio #: 22-3004-009-0170
Gentlemen:
In accordance with ordinance section 8-11( f ), this office has inspected the building located at the
above address.
This office has visually examined the building and presents the attached inspection report.
There are NO RECOMMENDED REPAIRS indicated within this report.
We find the building to be ELECTRICALLY SAFE FOR ITS USE AND PRESENT OCCUPANCY,
and recommend re certification for the above noted project
As a routine matter, & in order to avoid possible misunderstandings, nothing in this report should be
construed directly or indirectly as a guarantee for any portion of the building.
To the best of our knowledge and ability, this report represents an accurate appraisal of the present
condition of the building based upon careful evaluation of observed conditions, to the extent
reasonably possible.
Should any question arise, please feel free to call. It has been a pleasure to serve you.
Respectfully submitted,
Tupack Rhea, P.E.
Professional Engineer
Regulatory and Economic Resources
11805 SW 26th Street
Miami, Florida 33175-2474 786-315-2000
miamidade.gov/building
☐
CERTIFICATION OF COMPLIANCE WITH PARKING LOT ILLUMINATION
STANDARDS IN CHAPTER 8C-3 OF THE CODE OF MIAMI -DADE COUNTY
Date:
Case No._______________ FYear
PropertyAddress: , Bldg. No.: , Sq. Ft.:
Folio Number:
Building Description:
1. I am a Florida registered professional engineer architect with an active license.
2.On, 20 at AM PM, I measured the level of illumination in the parking
lot(s) serving the above referenced building.
3.Maximum foot candle
Minimum foot candle
Maximum to Minimum Ratio : , foot candle
4.The level of illumination provided in the parki ng lot meets does not meet the
minimum standards for the occupancy classification of the building as established in Section 8C-3
of Miami -Dade County Code.
Signature and Seal of Professional Print Name Engineer or Architect
BORA Approved – Revised November 18, 2021 Page 1 of 9 12/21R1.0
REGULATORY AND ECONOMIC RESOURCES DEPARTMENT
11805 SW 26th Street, Miami, Florida 33175
786-315-2000
Miamidade.gov/building
CASE REFERENCE NUMBER:
JURISDICTION NAME:
LICENSEE NAME:
TITLE:
ADDRESS:
SIGNATURE:
*Use separate sheets for additional responses by referencing the report number.
1. DESCRIPTION OF BUILDING
a. Name on Title:
b. Building Street Address: Bldg. #:
c. Legal Description: Attached: ܆
d. Owner’s Name:
e. Owner’s Mailing Address:
f. Folio Number of Property on which Building is Located:
g. Building Code Occupancy Classification:
h. Present Use:
i. General Description of building (overall description, structural systems, special features):
j. Number of Stories: k. Is this a Threshold Building as per 553.71(12) F.S. (Yes/No):
l. Provide an aerial of the property identifying the building being certified on a separate sheet. Attached: տ
m. Additional Comments:
MINIMUM INSPECTION PROCEDURAL GUIDELINES
FOR BUILDING ELECTRICAL RECERTIFICATION
TUPACK RHEA
PROFFESSIONAL ENGINEER
12310 SW 39 ST
MIAMI DADE FLORIDA 33175
PBR22-0053
TOWN OF MEDLEY
TA MEDLEY COMERCE CENTER
9305-9395 NW 101 ST H
LOTS 15-21 BLK1 OF MEDLEY COMMERCE&IND CENT PB ✔
TA MEDLEY COMMERCE CENTER
1 FEDERAL STREET 17 FL BOSTON MA 02110
22-3004-009-0170
LIGHT MANUFACTERING
MANUFACTERING/STORAGE
ONE STORY, 102,382 SQ FT BUILDING, PREFABRICATED DOUBLE "T" EXTERIOR WALLS ON
SPREAD FOOTING FOUNDATION WITH PREFABRICATED DOUBLE "T" ROOFING SYSTEM AND
A TPO ROOFING MEMBRANE.
1 No
✔
NONE
BORA Approved – Revised November 18, 2021 Page 2 of 9 12/21R1.0
2.INSPECTIONS
a.Date of Notice of Required Inspection:
b.Date(s) of actual inspection:
c.Name and qualifications of licensee submitting report:
d.Are Any Electrical Repairs Required? (YES/NO):
1.If required, describe, and indicate acceptance:
e.Can the building continue to be occupied while recertification and repairs are ongoing? (YES/NO):
1.Explanation/Conditions:
3.ELECTRICAL SERVICE
a.Size:Voltage ( ) Amperage ( ) Type: Fuses ( ) Breakers ( )
b.Phase:Three-Phase ( ) Single Phase ( )
c.Condition:Good ( ) Fair ( ) Needs Repair ( )
Comments:
4.METERING EQUIPMENT
1.Clearances:Good ( ) Fair ( ) Needs Correction ( )
Comments:
PROVIDE PHOTO
PROVIDE PHOTO
6/28/2023
7/13/2024-10/7/2024
TUPACK RHEA P.E.; PROFESSIONAL ENGINEER
No
n/a
Yes
208/12 * x
6 UNDERGROUND SERVICES 500 A 208/120V 3PHASE
1000 A 208/120V 3PHASE
(4) 400 A 120/208V 3 PHASE.
BORA Approved – Revised November 18, 2021 Page 3 of 9 12/21R1.0
5. ELECTRIC ROOMS
1. Clearances: Good ( ) Fair ( ) Needs Correction ( )
Comments:
6. GUTTERS
1. Location: Good ( ) Needs Repair ( )
2. Taps and Fill: Good ( ) Needs Repair ( )
Comments:
7. ELECTRICAL PANELS
1. Panel # ( ) Location:
Good ( ) Needs Repair ( )
2. Panel # ( ) Location:
Good ( ) Needs Repair ( )
3. Panel # ( ) Location:
Good ( ) Needs Repair ( )
4. Panel # ( ) Location:
Good ( ) Needs Repair ( )
5. Panel # ( ) Location:
Good ( ) Needs Repair ( )
PROVIDE PHOTO
PROVIDE PHOTO PROVIDE PHOTO
PROVIDE PHOTO
n/a
9325 Inside warehouse
9335 INSIDE WAREHOUSE
9305 INSIDE WAREHOUSE
9375 INSIDE WAREHOUSE
9385 INSIDE WAREHOUSE
BORA Approved – Revised November 18, 2021 Page 4 of 9 12/21R1.0
Comments:
8. BRANCH CIRCUITS
1. Identified: Yes ( ) Must be Identified ( )
2. Conductors: Good ( ) Deteriorated ( ) Must be Replaced ( )
Comments:
9. GROUNDING OF SERVICE
Good ( ) Needs Repair ( )
Comments:
10. GROUNDING OF EQUIPMENT
Good ( ) Needs Repair ( )
Comments:
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
PANELS INSIDE THE WAREHOUSE UNITS IN GOOD CONDITION.
BORA Approved – Revised November 18, 2021 Page 5 of 9 12/21R1.0
11. SERVICE CONDUIT/RACEWAYS
Good ( ) Needs Repair ( )
Comments:
12. GENERAL CONDUIT/RACEWAYS
Good ( ) Needs Repair ( )
Comments:
13. WIRE AND CABLES
Good ( ) Needs Repair ( )
Comments:
14. BUSWAYS
Good ( ) Needs Repair ( )
Comments:
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
N/A
BORA Approved – Revised November 18, 2021 Page 6 of 9 12/21R1.0
15. THERMOGRAPHY INSPECTION RESULTS
(ADD SHEETS AS REQUIRED)
Comments:
16. OTHER CONDUCTORS
Good ( ) Needs Repair ( )
Comments:
17. TYPES OF WIRING METHODS
1. Conduit Raceways Rigid: Good ( ) Needs Repair ( ) N/A ( )
2. Conduit PVC: Good ( ) Needs Repair ( ) N/A ( )
3. NM Cable: Good ( ) Needs Repair ( ) N/A ( )
4. Other: Good ( ) Needs Repair ( ) N/A ( )
a. Other Wiring (Specify):
Comments:
18. EMERGENCY LIGHTING
Good ( ) Needs Repair ( ) N/A ( )
Comments:
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
SEE ATTACHED, ALL CONDITIONS NORMAL, NO ANOMALIES.
BORA Approved – Revised November 18, 2021 Page 7 of 9 12/21R1.0
19. BUILDING EGRESS ILLUMINATION
Good ( ) Needs Repair ( ) N/A ( )
Comments:
20. FIRE ALARM SYSTEM
Good ( ) Needs Repair ( ) N/A ( )
Comments:
21. SMOKE DETECTORS
Good ( ) Needs Repair ( ) N/A ( )
Comments:
22. EXIT LIGHTS
Good ( ) Needs Repair ( ) N/A ( )
Comments:
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
BORA Approved – Revised November 18, 2021 Page 8 of 9 12/21R1.0
23. EMERGENCY GENERATOR
Good ( ) Needs Repair ( ) N/A ( )
Comments:
24. WIRING IN OPEN OR UNDER COVER PARKING GARAGE AREAS
Good ( ) Requires Additional Illumination ( ) N/A ( )
Comments:
25. OPEN OR UNDER COVER PARKING GARAGE AND EGRESS ILLUMINATION
Good ( ) Requires Additional Illumination ( ) N/A ( )
Comments:
26. SWIMMING POOL WIRING
Good ( ) Needs Repair ( ) N/A ( )
Comments:
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
PROVIDE PHOTO
BORA Approved – Revised November 18, 2021 Page 9 of 9 12/21R1.0
27. WIRING TO MECHANICAL EQUIPMENT
Good ( ) Needs Repair ( ) N/A ( )
Comments:
28. ADDITIONAL COMMENTS
PROVIDE PHOTO
Reset Form
Location:
ELECTRICAL
ROOM
Condition:
GOOD
Date:
09/5/24
Description:
METERS
SERVICE
CONDUIT
PHOTOGRAPH
1
Location:
ELECTRICAL
ROOM
Condition:
GOOD,
Date:
09/5/24
Description:
METERS
GUTTERS
SERVICE
CONDUIT
PHOTOGRAPH
2
Location:
ELECTRICAL
ROOM
Condition:
GOOD
Description:
ELECTRICAL
ROOM
SERVICE
CONDUIT
Date:
09/5/24
PHOTOGRAPH
3
Location:
OFFICE
Condition:
GOOD,
Description:
PANEL
Date:
9/5/24
PHOTOGRAPH
4
Location:
WAREHOUSE
Condition:
GOOD,
Description:
PANEL
Date:
9/5/24
PHOTOGRAPH
5
Location:
WAREHOUSE
Condition:
GOOD,
Date:
9/5/24
Description:
PANEL
PHOTOGRAPH
6
Location:
WAREHOUSE
Condition:
GOOD,
Date:
9/5/24
Description:
PANEL
PHOTOGRAPH
7
Location:
WAREHOUSE
Date:
9/5/24
Description:
PANEL
PHOTOGRAPH
8
Location:
WAREHOUSE
Date:
9/5/24
Description:
PANEL
PHOTOGRAPH
9
Location:
WAREHOUSE
Date:
9/5/24
Description:
PANEL
PHOTOGRAPH
10
Location:
ELECTRICAL
ROOM
Date:
9/5/24
Description:
GROUNDING
PHOTOGRAPH
11
Location:
WAREHOISE
Date:
9/5/24
Description:
CONDUITS/
RACEWAYS
PHOTOGRAPH
12
Location:
WAREHOUSE
Date:
9/5/24
Description:
CONDUITS/
RACEWAYS
EXIT SIGN
EMERGENCY
LIGHT
PHOTOGRAPH
13
Location:
WAREHOUSE
Date:
9/5/24
Description:
CONDUITS/
RACEWAYS
PHOTOGRAPH
14
Location:
WAREHOUSE
Date:
9/5/24
Description:
CONDUITS/
RACEWAYS
PHOTOGRAPH
15
Location:
WAREHOUSE
Date:
9/5/24
Description:
CONDUITS/
RACEWAYS
PHOTOGRAPH
16
Location:
EXTERIOR
Date:
9/5/24
Description:
WIRE AND
CABLES
PHOTOGRAPH
17
Location:
OFFICE
Date:
9/5/24
Description:
EXIT SIGN
EMERGENCY
LIGH
PHOTOGRAPH
18
Location:
WAREHOUSE
Date:
9/5/24
Description:
EMERGENCY
LIGHT
EXIT SIGN
PHOTOGRAPH
19
Location:
OFFICE
Date:
9/5/24
Description:
EMERGENCY
LIGHT
EXIT SIGN
PHOTOGRAPH
20
Location:
WAREHOUSE
Date:
9/5/24
Description:
EMERGENCY
LIGHT
EXIT SIGN
PHOTOGRAPH
21
Location:
WAREHOUSE
Date:
9/5/24
Description:
EMERGENCY
LIGHT
EXIT SIGN
PHOTOGRAPH
22
Location:
WAREHOUSE
Date:
9/5/24
Description:
EMERGENCY
LIGHT
EXIT SIGN
PHOTOGRAPH
23
Location:
OFFICE
Date:
9/5/24
Description:
EMERGENCY
LIGHT
EXIT SIGN
PHOTOGRAPH
24
Location:
EXTERIOR
Date:
9/5/24
Description:
EGRESS
ILUMINATION
PHOTOGRAPH
25
Location:
EXTERIOR
Date:
9/5/24
Description:
EGRESS
ILUMINATION
PHOTOGRAPH
26
Location:
EXTERIOR
Date:
9/5/24
Description:
PARKING
ILUMINATION
PHOTOGRAPH
27
Location:
EXTERIOR
Date:
9/5/24
Description:
PARKING
ILUMINATION
PHOTOGRAPH
28